49
[ 2 ] Strobe Signal (Input)
(1) Function
This signal informs the Robot Controller that the command area, data areas
1 and 2, and the command and data area odd parity bit have been set.
Additionally it directs the start of command processing.
Caution: Perform command input with a strobe signal after the system
output signal ROBOT INITIALIZATION COMPLETE is output.
(2) Terminal number
No. 8 of connector CN8.
(3) Input conditions and operation
By turning ON this input in automatic or external mode, the Robot
Controller reads the command area, data areas 1 and 2, and the
command and data area odd parity bit starts processing.
Retain the status until a command processing complete signal is output
and the necessary status data is read. If the strobe signal is turned OFF
before a command processing complete signal is output, the status area
will not be output.
By turning OFF this input after the status is read, the command
processing complete output, the status area and the status parity will be
turned OFF.